top of page

Zero-Downtime VFD Replacement for a Chilled Water Plant

Writer: Craig Drabyk
Craig Drabyk
2 days ago
3 min read

As part of a larger project, an existing mechanical room needed to be expanded. That meant moving a wall that housed six critical 125 HP variable frequency drives (VFDs) running the facility’s chilled water plant. These drives powered the large pumps that circulate water through two 1,200-ton chillers. The challenge was to relocate the VFDs with little to no interruption to the chilled water serving the facility.


New 125 HP VFDs installed in mechanical room

The Challenge: Keeping Chilled Water Running

The client was understandably uneasy. Chilled water is the lifeblood of the facility. It supports occupant comfort and critical processes, so even a short outage was a serious risk.


After weighing all available options, Omni developed a plan that called for zero interruption and no downtime. We put the plan in writing as a detailed Method of Procedure (MOP) and presented it to the client.


Why Replacing the VFDs Made More Sense Than Moving Them

The six existing VFDs were 16 years old, fairly large, and nearing the end of their life expectancy. Rather than relocate aging equipment, Omni recommended a VFD replacement.


Through our VFD vendor, new 125 HP drives were available in four weeks or less. The new drives also had a much smaller footprint. Four fit neatly into an ideal corner location, and the remaining two were mounted beside a nearby distribution panel.


Preparing the New Drives Before Cutover

The MOP called for installing and wiring the line and load sides of all six new drives, along with each drive’s control I/O. Before the drives were energized, we programmed each drive’s CPU for its associated pump using a separate 24V power source. We intercepted power in a large electrical trough and ran the new I/O wiring to the existing control junction boxes.


Doing this work ahead of time meant the new VFDs were ready to go before any pump was taken offline.


Using N+1 Redundancy to Swap One Pump at a Time

The drives operated in an N+1 configuration, with two of three running continuously and one serving as standby. This applied to both the chilled water and condenser water pumps.


That redundancy was the key to a zero-downtime VFD replacement. Omni’s VFD technician, working alongside the client’s BAS team, was able to bump and check rotation, start up, commission, and swap over one 125 HP pump at a time. Throughout the process, we ensured the system maintained differential pressure and proper flow through each chiller and the system.


Why a Detailed Method of Procedure Matters

Every step was preplanned and documented in the MOP. It laid out the exact sequence of events, who was involved, and the time required for each activity. Each MOP is reviewed with everyone involved before any work begins, so the whole team knows what happens next and who is responsible.


The Results: Six New VFDs and Zero Downtime

Swapping over and verifying all six pumps was completed in a 10-hour period. The MOP went exactly as planned, with zero downtime.


The client now has new VFDs, plus AEGIS shaft grounding rings protecting the bearings on each large motor. Pleased with the planning, execution, and results, the client has adopted the detailed MOP as a standard operating procedure going forward.


Planning a VFD replacement or upgrade in a facility that can’t afford downtime? Contact Omni to talk through your project.

 
 
 

Comments


© 2024 Omni Instrumentation & Electrical Services, Inc.

  • Grey Facebook Icon
  • Grey Google+ Icon
  • Grey Instagram Icon

Website by: Classy Websites NJ/NYC

bottom of page